21 building management systems items from the Board of Chief Engineers, Government of Andhra Pradesh, effective 2026-06-01.

Building Management Systems rates in the Andhra Pradesh Common Schedule of Rates — Part-III (Buildings, Water Supply & Electrical) 2026-27 run from ₹2,255.00 to ₹7,15,000.00. Transcribed from Government of Andhra Pradesh — Common Schedule of Rates 2026-27, Part-III (Buildings), Board of Chief Engineers. Reference only — verify against the official source before pricing a bid.

21 items — scroll the table to browse

DescriptionUnit
ELEC-14.3.1Supply, Installation, Testing & Commissioning of BMS server with following latest Intel microprocessor Xeon or higher processor, 2.7 to 3.0Ghz or above clock speed, 16 GB expandable up to 32GB DDR 4 RAM,HDD - 1TB SATA, R/W CD / DVD drive, Flat Monitor - 32" LED, Serial Ports - 2 Nos, USB Ports - 4 Nos, Network Card 10/100/1000MB, Graphics card 1GB, Windows Operating System-Higher version, MS office suite Anti virus, Optical mouse & key board etc.as per detailed technical specifications and approved make including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsSet4,34,500.00
ELEC-14.3.2Supply, Installation, Testing & Commissioning of BMS Client Workstation with following Latest Intel microprocessor i7 / higher , 2.7 to 3.0Ghz or above clock speed, 8GB expandable up to 32GB DDR 4 RAM, HDD - 1TB SATA ,R/W CD / DVD drive, Flat Monitor - 32" LED, Serial Ports - 2 Nos. USB Ports - 4 Nos with at least 2 NOs USB 3.0 Ports, Network Card 10/100/1000MB - 2 Nosography card 1GB,Windows 10 Operating System / Higher, MS office suite Anti virus, Optical mouse & key board etc.as per detailed technical specifications and approved. Makes: As per list of recommended brandsSet1,04,500.00
ELEC-14.3.3Supply, Installation, Testing & Commissioning of Building Control System Software - MAIN BMS SERVER SOFTWARE, of the following windows based graphical software for IBMS system with 1No Client for Operator workstation, 1No Client for Engineer workstation. The Software shall have 3D & HD vector dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility, Native 64 Bit System , BTL,UL,EN Certified System, BACnet Profile B-AWS (Advanced workstation) as per the BTL Listing, dot net platform, Certified OPC DA Server by OPC Foundation, Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Chrome, Firefox, Netscape Navigator, etc. The Software shall comply to international standards and strive to deliver products that meet security standards such as ISA/IEC 62443, UL2900, ISO/IEC 27001, ISO/IEC62443 and OWASP. Cybersecurity audit trail , 4-eye principle , Seamless integration of certificates within customer IT infrastructure, Microsoft’s active directory-based authentication, Use of network infrastructure that supports physical network or VLAN segmentation, Placing the web server in a “demilitarized zone” (DMZ), End-to-end encryption, from client to server, End-to-end encryption between servers, Certificate-based data exchange, Encrypted backups. The software shall have the capability to integrate with BIM Modelling. The software shall be Energy Conservation CalculationSet7,15,000.00
ELEC-14.3.4DDC for Air Handling Unit -( 2 AHU per DDC)- Supply, Installation, Testing & Commissioning of 32 Bit Microprocessor true IP Based DDC supporting and I/O's designed as per the IO Summary with all other mounting accessories, The controller shall have inbuilt 2-port Ethernet switch . The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules, The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. Each DDC should contain 20% spare IO for each type of below mentioned IO's. DDC Internal Cabling shall be BMS vendor scope. For more Details, Please refer IO Summary and as per detailed technical specifications and approved make including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsSet68,200.00
ELEC-14.3.5DDC for OT - Air Handling Unit - (1 AHU per DDC)- SITC of True IP Based DDC Standalone 32 Bit Intelligent, peer to peer communication, interoperable DDC as per the specification. The compact controller shall have inbuilt 2-port Ethernet switch with WLAN interface. The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules. The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. The controller shall be freely programmable and have System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories). It should have Cloud connectivity for remote access and inbuilt port for POT for local interface. Makes: As per list of recommended brandsSet62,091.00
ELEC-14.3.6DDC for Ventilation and Lift Lobby Pressurization Fans- (4 Fans per DDC)- SITC of True IP Based DDC Standalone 32 Bit Intelligent, peer to peer communication, interoperable DDC as per the specification. The compact controller shall have inbuilt 2-port Ethernet switch with WLAN interface. The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules. The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. The controller shall be freely programmable and have System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories). It should have Cloud connectivity for remote access and inbuilt port for POT for local interface. Makes: As per list of recommended brandsSet60,716.00
ELEC-14.3.7DG - SITC of True IP Based DDC Standalone 32 Bit Intelligent, peer to peer communication, interoperable DDC as per the specification. The compact controller shall have inbuilt 2-port Ethernet switch with WLAN interface. The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules. The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. The controller shall be freely programmable and have System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories). It should have Cloud connectivity for remote access and inbuilt port for PO. Makes: As per list of recommended brandsSet66,550.00
ELEC-14.3.8DDC for Transformer/HT/LT- Supply, Installation, Testing & Commissioning of 32 Bit Microprocessor true IP Based DDC supporting and I/O's designed as per the IO Summary with all other mounting accessories, The controller shall have inbuilt 2-port Ethernet switch . The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules,The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. EachEach1,98,520.00
ELEC-14.3.9DDC for Lifts- Supply, Installation, Testing & Commissioning of 32 Bit Microprocessor true IP Based DDC supporting and I/O's designed as per the IO Summary with all other mounting accessories, The controller shall have inbuilt 2-port Ethernet switch . The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules, The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. Each DDC should contain 20% spare IO for each type of below mentioned IO's. DDC Internal Cabling shall be BMS vendor scope. For more Details, Please refer IO Summary.as per detailed technical specifications and approved make including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsEach66,550.00
ELEC-14.3.10DDC for Plumbing System & Fire Fighting - Supply, Installation, Testing & Commissioning of 32 Bit Microprocessor true IP Based DDC supporting and I/O's designed as per the IO Summary with all other mounting accessories, The controller shall have inbuilt 2-port Ethernet switch . The controller shall have 16 inputs/outputs inbuilt and can be expandable upto max 40 points by Input/Output Modules, The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 512 MByte NAND Flash. Each DDC should contain 20% spare IO for each type of below mentioned IO's. DDC Internal Cabling shall be BMS vendor scope. For more Details, Please refer IO Summary,. As per detailed technical specifications and approved make including all charges complete etc as directed by Engineer In charge/ departmental authoritiesEach63,800.00
ELEC-14.3.11Software Integration- SITC of True IP Based BTL & UL Listed for third party integration for AHU VFD's, VRV System, Thermostats, DG/UPS/LT/HT Panel and Fire Alarm Systems. The controller shall have 2- port Ethernet switch and WLAN interface. It should have BTL label (BACnet communications passed the BTL test) and consisting of Dual microprocessor with Storage capacity of 1 GB RAM. It should support Real Time clock upto 7 Days. It should Support of the major communication protocols: BACnet,/IP, BACnet MS/TP, Modbus IP and Modbus RTU upto 500 points. Integrator shall be of same make only. Makes: As per list of recommended brandsJob2,75,000.00
ELEC-14.3.12Supply, Installation, Testing & Commissioning of Ambient Temperature + RH Sensor with all the mounting accessories included. Temp sensor shall be Pt 1000 RTD type with 4 to 20mA transmitter or thermistor type and RH sensor shall be capacitive type with 4 to 20mA transmitter. The temperature measurement range shall be 0 to 50oC and humidity range shall be 0 to 95% RH as technical specification with all other mounting accessories complete as required including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsEach20,684.00
ELEC-14.3.13Supply, fixing, Testing & Commissioning of Room Type Temperature + Humidity Sensor including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsNos15,048.00
ELEC-14.3.14Supply, Installation, Testing & Commissioning of Differential Pressure Switch (DPS ) with all the mounting accessories included. The maximum pressure limit shall be 0-1000Pa as technical specification with all other mounting accessories complete as required. Field Devices & internal cabling of AHU shall be BMS vendor scope including all charges complete etc as directed by Engineer In charge/ departmental authoritiesEach2,696.00
ELEC-14.3.15Supply, Installation, Testing & Commissioning of Duct Static Pressure Sensor with all the mounting accessories included. The maximum pr limit shall be 0-500Pa all other mounting accessories complete as required. Field Devices & internal cabling of AHU shall be BMS vendor scope including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsEach7,534.00
ELEC-14.3.16Supply, fixing, Testing & Commissioning of Duct Temperature Sensors including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsNos3,733.00
ELEC-14.3.17Supply, installation, testing and commissioning of Return air CO2 Sensor including all charges complete etc as directed by Engineer In Charge/ departmental authorities. Makes: As per list of recommended brandsEach17,365.00
ELEC-14.3.18Supply, fixing, Testing & Commissioning of Current Relay including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsNos2,255.00
ELEC-14.3.19Supply, fixing, Testing & Commissioning of Voltage Transducer including all charges complete etc as directed by Engineer In charge/ departmental authorities. Makes: As per list of recommended brandsEach7,150.00
ELEC-14.3.20Supply, fixing, Testing & Commissioning of Ultrasonic Water Level Sensor (Note: Level should indicate as Litre basis in BMS Screen) for Water tank as technical specification with all other mounting accessories including all charges complete etc as directed by Engineer In Charge/ departmental authorities. Makes: As per list of recommended brandsEach21,437.00
ELEC-14.3.21Supply, fixing, Testing & Commissioning of Flame Proof Diesel Level Sensor for Diesel Day Tank Monitoring. Tank Height 1 Mtr including all chargesEach13,594.00

Other chapters in this schedule

Pricing building management systems against a live tender

Mapping a tender BOQ to the right schedule items, applying the current cost index, and catching where rates have moved since the base edition is slow and easy to get wrong. Arched's estimation engine reads the tender, maps it to the applicable schedule, and flags where the numbers are exposed before submission.